Model: NTI-FIB-TFIB | Category: Hydrant Hardware
Tulsi Fire Inlet Breeching (2-Way & 4-Way)
Tulsi Fire Inlet Breechings are installed at ground level outside multi-story buildings, industrial plants, and refineries to enable municipal fire brigade pumping engines to augment water supply into the internal riser piping system. Features individual spring-loaded brass NRVs in each inlet port.
Features & Compliance
- Complies with IS 904 and international fire codes BS 5041
- Independent non-return valves prevent backflow into open ports
- Integrated drain valve prevents stagnant freeze or corrosion in dry riser
- Supplied complete with blank caps and retaining chains
Technical Specifications
Verified test benchmarks and dimensions conforming to Indian Standards.
| Inlet Ports | 2-Way (2 x 63 mm) or 4-Way (4 x 63 mm) Instantaneous Male with NRV |
| Outlet Connection | 100 mm (4 inch) or 150 mm (6 inch) NB PN16 Flanged |
| Material of Body | Ductile Cast Iron / Cast Carbon Steel / Gunmetal |
| Valve Elements | Spring-loaded Gunmetal NRV with resilient neoprene seals |
| Drain Valve | 1 inch bronze ball drain valve to bleed trapped riser column |
| Test Pressure | 21 kgf/cm² |
All units supplied with MTC (Manufacturer Test Certificate) and serialized batch hydrostatic inspection reports.